✉ sales@juduncp.com ☎ +86 153 0327 5365 / +86-317-6220889 ISO 9001 · ISO 14001 · ISO 45001 Certified | 12 Patents & Software Copyrights
← Ко всем статьям (Обзор продукции)

Solid-State Decoupler (SSD) vs. Isolating Spark Gap vs. Drainage Bond: Which Do You Need?

Обзор продукции
Solid-State Decoupler (SSD) vs. Isolating Spark Gap vs. Drainage Bond: Which Do You Need?

Clear engineering breakdown of when to specify an Isolating Spark Gap for lightning-only isolation versus an SSD for continuous AC mitigation or a Polarized Bond for DC rail stray current.

While Solid-State Decouplers (SSD), Isolating Spark Gaps (ISG), and Polarized Drainage Bonds all connect protected pipelines to grounding systems or across insulating joints, each solves a distinct electrical hazard:

  • Isolating Spark Gap (ISG): Remains completely open-circuit during normal AC/DC operation and fires only during lightning strikes or kV-level surges. Specify ISGs across insulating flanges/joints where steady-state induced AC is negligible.
  • Solid-State Decoupler (SSD / Ex-SSD): Blocks CP DC within its -2V / +2V window while continuously shunting steady-state induced 50/60Hz AC current (45A–100A rms) AND clamping 100kA lightning surges. Essential for pipelines sharing corridors with HV AC transmission lines.
  • Polarized / Intelligent Drainage Units: Designed for DC traction stray current zones (metro/DC rail), draining anodic stray DC unidirectionally while blocking reverse current pickup.