Steady-state induced AC potentials up to 38V AC and >120 A/m² AC current density were reduced below 6V AC and <20 A/m² using JUDUN SSD decouplers, zinc ribbon mats, and 4G monitoring.
Project Challenge
A 42 km section of DN800 high-pressure natural gas pipeline shared a narrow right-of-way (35 m minimum separation) with double-circuit 220 kV overhead transmission lines. Baseline surveys recorded steady-state pipe-to-soil AC voltages of 26V – 38V AC and 1 cm² coupon AC current densities exceeding 120 A/m²—posing both personnel shock hazards and rapid AC corrosion risk.
JUDUN Engineering Package
- Installed 24 Solid-State Decouplers (
SSD-50-100-B302015at right-of-way peaks andEx-SSDunits inside hazardous valve stations); - Constructed low-impedance horizontal grounding mats using ASTM B418 Type II Zinc Ribbon Anodes alongside the trench;
- Deployed 12 Wireless 4G Potential Data Loggers with
1 cm²AC density coupons for continuous compliance verification.
Verified Field Results
Post-commissioning steady-state AC voltages dropped across all 42 km to 2.8V – 5.6V AC (well below the 15V NACE limit), AC current density fell below 18 A/m², and instant-off DC cathodic protection potentials remained solidly between -0.96V and -1.12V vs. CSE.