✉ sales@juduncp.com ☎ +86 153 0327 5365 / +86-317-6220889 ISO 9001 · ISO 14001 · ISO 45001 Certified | 12 Patents & Software Copyrights
Atténuation des Interférences et Parafoudres

Solid-State Decoupler (SSD)

Applicable Standards: NACE SP0177, ISO 18086, EN 50162, IEC 60079-1 (Ex), GB/T 50698

Blocks cathodic protection DC current while providing a low-impedance path to ground for induced steady-state AC current, AC fault surges, and lightning transients.

Typical Field Applications: HV power line shared corridors, AC/DC electrified railway stray current zones, and insulating joint lightning surge protection

Spécifications Techniques

DC Blocking Threshold-2.0 V / +2.0 V (Optional -3.0 V / +1.0 V)
Steady-State AC Current45 A / 60 A / 80 A / 100 A rms continuous
AC Fault Current (30 cyc)3.7 kA / 5.0 kA rms @ 30 cycles
Lightning Surge Rating100 kA crest (8/20 μs)
Enclosure ProtectionIP65 / IP68 Submersible & Weatherproof

Modèles Standards

Model Number Key Rating Dimensions & Configuration
SSD-50-100-B302015 50A AC / 100kA Surge / -2V~+2V 300 × 200 × 150 mm Stainless Enclosure
SSD-50-100-B403015 80A AC / 100kA Surge / -2V~+2V 400 × 300 × 150 mm Heavy Enclosure
MSSD-50/100 45A–50A AC / 100kA Compact Module Ø110 × 230 mm Test-Post Mountable

Related System Products

Zinc Ribbon Anode
Anodes Sacrificielles

Zinc Ribbon Anode

Extruded diamond-profile high-purity zinc ribbon with centralized steel wire core (ASTM B418 Type II), widely deployed alongside solid-state decouplers for AC mitigation grounding mats and cased pipeline crossings.

Specs
Flameproof Solid-State Decoupler (Ex-SSD)
Atténuation des Interférences et Parafoudres

Flameproof Solid-State Decoupler (Ex-SSD)

Hazardous-area certified Ex d IIC T6 Gb flameproof solid-state decoupler engineered for Zone 1 & Zone 2 gas stations, valve chambers, tank farms, and above-ground insulating joints.

Specs
Isolating Spark Gap (ISG)
Atténuation des Interférences et Parafoudres

Isolating Spark Gap (ISG)

Installed across pipeline insulating joints/flanges to maintain open-circuit DC/AC isolation under normal operation while firing instantaneously during lightning or HV surge events.

Specs
Indirect Equipotential Bonding Device
Atténuation des Interférences et Parafoudres

Indirect Equipotential Bonding Device

Provides indirect equipotential bonding between cathodically protected piping and station earthing grids—isolated during normal operation and instantaneously clamped under overvoltage faults.

Specs
💬 WhatsApp